NPL SERIES Valve Regulated Lead-Acid Batteries (VRLA)
The NPL range is an enhanced NP
design resulting in a longer service life (7 - 10yrs). All
other attributes and operational characteristics are the same,
thereby maintaining the benefit of a common mechanical and
electrical design for users of both products. Product Brochure & Data Sheets Please click here to view the range of Product Brochures and Data Sheets available to download
Features
Yuasa VRLA batteries can be used in any orientation
excluding continuous use inverted.
Standard case material is flame retardant to (UL94)
HBØ.
FR option case material is flame retardant to UL94:VØ
(oxygen index 30).
NPL batteries are manufactured in factories that comply
with ISO 9001:2000.
FR option NPLs comply with BS6290 Part 4 (1997).
NPL batteries comply with IEC 60896-21+22.
Layout *Models
available in Flame Retardent case only.
click
on layouts for larger images
Terminals
click
for larger image
General Specifications
Nominal
Capacity (Ah)
NPL130-6IFR
NPL24-12I
NPL38-12I
NPL65-12I
NPL78-12IFR
NPL100-12
NPL200-6
20hr
to 1.75vpc 20°C
130
24
38
65
78
100
200
10hr
to 1.75vpc 20°C
120
22.3
35.3
60.5
72.6
93
186
5hr
to 1.70vpc 20°C
110
20.4
32.3
55.3
66.3
84
168
1hr
to 1.60vpc 20°C
78
14.4
22.8
39
46.8
60
120
Voltage
6
12
12
12
12
12
6
Energy
Density (Wh/L)
77
79
83
77
85
75
71.64
Specific
Energy (Wh. kg)
34
32
32
34
34
29
28.3
Int
Resistance (m.ohms)
2.5
9.5
7.5
5
<5
4
1.3
Maximum
discharge (A)
390
150
200
500
500
500
600
Short
Circuit current
800
500
500
800
800
800
1500
Dimensions
(mm) +/- 2mm
Length
350
166
197
350
380
407
407
Width
166
175
165
166
166
172
172
Height
overall
174
125
170
174
174
240
240
Weight
(Kg)
23
9
14.2
23
27.5
39
39
Terminal
C
B
B
C
D
E
E
Torque
(Nm)
4.76
2.45
2.45
4.76
6.1
16.5
16.5
Operational Temperature
Range
Charge:
15~ 50°C
Discharge:
20°C to 60°C
Storage:
20°C to 50°C (fully charged
condition)
Applications
Security and Fire
UPS
Telecoms
Emergency Lighting
click
on graph for larger image
click
on graph for larger image
click
on graph for larger image
click
on graph for larger image
click
on graph for larger image
Charging
Methods (at 20°C)
Standby use: Float charging voltage 2.275vpc
CAUTION
- Avoid short circuit.
- Do not charge in a sealed container.
- Service life and operational characteristics will be affected
by temperature.
- AC Ripple reduces service life.